Velocity Edge GX440 Instructions d'exploitation Page 415

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 530
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 414
Diagnosis / faults and alarms
10.2 Diagnosis
Drive converter cabinet units
Operating Instructions, 10/2008, A5E00288214A
415
LED Color State Description
--- OFF Cyclic communication is not (yet) running.
Note:
The PROFIdrive is ready for communication when the Control Unit
is ready for operation (see RDY LED).
Steady light Cyclic communication is running. Green
0.5 Hz flashing
light
Cyclic communication is not yet fully underway.
Possible causes:
- The controller is not transmitting any setpoints.
- In isochronous mode, the controller did not send a Global Control
or it sent a defective Global Control (GC).
Red Steady light Cyclic communication has been interrupted.
DP1
(PROFIdrive cyclic
transmission)
Orange 2 Hz flashing light Firmware checksum error (CRC error).
--- OFF Electronic power supply outside permissible tolerance range.
The component is not ready for operation.
The Option Board is missing or an associated drive object has not
been created.
Steady light Option Board is ready. Green
0.5 Hz flashing
light
Depends on the Option Board used.
OPT
(option)
Red Steady light At least one fault is pending on this component.
The Option Board is not ready (e.g., after switching on).
MOD --- OFF Reserved
Customer Terminal Block TM31 (-A60)
Table 10- 2 Description of the LEDs on the TM31
LED Color State Description
--- OFF The electronics power supply is missing or lies outside permissible
tolerance range.
Green Steady light The component is ready for operation and cyclic DRIVE-CLiQ
communication is taking place.
Orange Steady light DRIVE-CLiQ communication is being established.
Red Steady light At least one fault is pending on this component.
Note:
LED is driven irrespective of the corresponding messages being
reconfigured.
0.5 Hz flashing
light
Firmware is being downloaded. Green / red
2 Hz flashing
light
Firmware download is complete. Waiting for POWER ON.
RDY
Green orange
or
red orange
2 Hz flashing
light
Detection of the components via LED is activated (p0154).
Note:
Both options depend on the LED status when module recognition is
activated via p0154 = 1.
Vue de la page 414
1 2 ... 410 411 412 413 414 415 416 417 418 419 420 ... 529 530

Commentaires sur ces manuels