Commissioning
5.6 Status after commissioning
Drive converter cabinet units
176 Operating Instructions, 10/2008, A5E00288214A
5.6 Status after commissioning
LOCAL mode (control via operator panel)
You switch to LOCAL mode by pressing the "LOCAL/REMOTE" key.
Control (ON/OFF) is carried out via the "ON" and "OFF" keys.
You specify the setpoint using the "increase" and "decrease" keys or by entering the
appropriate numbers using the numeric keypad.
Analog outputs
The actual speed (r0063) is output as a current output in the range 0 to 20 mA at analog
output 0 (X522:2 and 3).
A current of 20 mA is equal to the maximum speed in p1082.
The actual current value (r0068) is output as a current output in the range 0 to 20 mA at
analog output 1 (X522:5 and 6).
A current of 20 mA corresponds to the current limit (p0640), which is set to 1.5 x the rated
motor current (p0305).
Digital outputs
The "enable pulses" signal is output at digital output 0 (X542:2 and 3).
The “no fault active” signal is output at digital output 1 (X542:5 and 6) (fail safe).
The "ready to start" signal is output at digital output 8 (X541:2).