Velocity Edge GX440 Instructions d'exploitation Page 197

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 530
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 196
Operation
6.4 Command sources
Drive converter cabinet units
Operating Instructions, 10/2008, A5E00288214A
197
6.4 Command sources
6.4.1 "PROFIdrive" default setting
Requirements
The "PROFIdrive" default setting was chosen during commissioning:
STARTER:
"PROFIdrive"
AOP30:
"5: PROFIdrive"
Command sources
U0DVWHUFRQWURODFWLYH
5(027(352),%86352),1(7
/2&$/2SHUDWRUSDQHO67$57(5
%XWWRQ/2&$/5(027($23
$VVXPHPDVWHUFRQWURO67$57(5
,QWHUQDOFRQWURO
2SHUDWRUSDQHO$23
&RQWUROSDQHO67$57(5
352),%86352),1(7
,QSXWWHUPLQDOV$70
Figure 6-9 Command sources - AOP30 ←→ PROFIdrive
Priority
The command source priorities are shown in the diagram "Command sources -
AOP30←→PROFIdrive".
Note
The EMERGENCY STOP and motor protection signals are always active (regardless of the
command source).
All of the supplementary setpoints are deactivated for LOCAL master control.
Vue de la page 196
1 2 ... 192 193 194 195 196 197 198 199 200 201 202 ... 529 530

Commentaires sur ces manuels

Pas de commentaire