Commissioning
5.3 Procedure for commissioning via STARTER
Drive converter cabinet units
140 Operating Instructions, 10/2008, A5E00288214A
Configuring the motor – Selecting the motor type
Figure 5-18 Configuring the motor – Selecting the motor type
In the Name field, enter a name of your choice for the motor.
From the selection box next to Motor type: select the appropriate motor for your
application
In the Parallel connection motor field, enter the number of motors connected in parallel, if
necessary. Motors connected in parallel must be of the same type and size.