Functions, monitoring, and protective functions
9.4 Extended functions
Drive converter cabinet units
Operating Instructions, 10/2008, A5E00288214A
363
Tolerance window (p2722)
After switching on, the difference between the stored position and the actual position is
ascertained and, depending on the result, the following is triggered:
● Difference within the tolerance window -> the position is reproduced based on the current
actual encoder value.
● Difference outside the tolerance window -> an appropriate message (F07449) is output.
The tolerance window is preset to quarter of the encoder range and can be changed.
CAUTION
The position can only be reproduced if, in the powered-down state, if the encoder was
moved through less than half of the range that it can represent. For the standard EQN1325
encoder, this is 2048 revolutions or half a revolution for singleturn encoders.
Note
The ratio stamped on the gear rating plate is often just a rounded-off value (e.g.1:7.34). If, for
a rotary axis, it is not permissible to have any long-term drift, then the actual ratio of the gear
teeth must be requested from the gear manufacturer.
Several drive data sets
As of FW version V2.6, position tracking of the load gear can be activated in several drive
data sets.
● The load gear is DDS-dependent.
● Position tracking of the load gear is calculated only for the active drive data set and is
EDS-dependent.
● If position tracking is to be continued in different drive data sets with the same
mechanical relationships and the same encoder data sets, it must be activated explicitly
in all relevant drive data sets. Possible applications for drive data set changeover with
continued position tracking:
– Star/delta changeover
– Different ramp-up times/controller settings
● On changeover of the drive data set where the gear is changed, position tracking is
restarted, i.e. the behavior after changeover is the same as after a POWER ON.
● For identical mechanical relationships and the same encoder data set, DDS changeover
has no effect on the calibration status and reference point status.
Commentaires sur ces manuels