Velocity Edge GX440 Instructions d'exploitation Page 396

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 530
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 395
Functions, monitoring, and protective functions
9.4 Extended functions
Drive converter cabinet units
396 Operating Instructions, 10/2008, A5E00288214A
Fixed stop reached
As soon as the axis comes into contact with the mechanical fixed stop, the closedloop
control in the drive raises the torque so that the axis can move on. The torque increases up
to the value specified in the task and then remains constant. Depending on the binector input
p2637 (fixed stop reached), the "fixed stop reached" status bit r2683.12 is set if:
the following error exceeds the value set in parameter p2634 (fixed stop: maximum
following error) (p2637 = r2526.4)
external status via the signal at binector input p2637 (fixed stop reached), if this p2637 ≠
r2526.4
For traversing to fixed stop, the clamping torque in the traversing block is configured via the
task parameter. This is specified in units of 0.01 Nm. The function module is coupled to the
torque limit of the basic system via the connector output r2686[0] (torque limit upper) or
r2686[1] (torque limit lower), which are connected to the connector input p1528 (torque limit
upper scaling) or p1529 (torque limit lower scaling). The connector outputs r2686[0] (torque
limit upper) and r2686[1] (torque limit lower) are not set to 100 % during active fixed stop.
During an active fixed stop, r2686[0] (upper torque limit) or r2686[1] (lower torque limit) are
evaluated as p1522/p1523 in such a way that a limitation to the predefined clamping torque
is applied.
When the fixed stop is acknowledged (p2637), the "Speed setpoint total" (p2562) is
recorded, as long as the binector input p2553 (fixed stop reached message) is set. The
speed control holds the target torque on the basis of the available speed setpoint. The target
torque is output for diagnosis via the connector output r2687 (torque setpoint).
In the fixed stop, if the parameterized clamping torque has been reached, the status bit
r2683.13 "fixed stop clamping torque reached" is set.
Once the "fixed stop reached" status has been detected, the traversing task "traverse to
fixed stop" is ended. Block relaying is carried out in accordance with the parameterization.
The drive remains in fixed stop until the next positioning task is processed or the system is
switched to jog mode. The clamping torque is therefore also applied during subsequent
waiting tasks. The continuation condition CONTINUE_EXTERNAL_WAIT can be used to
specify that the drive should remain in fixed stop until an external signal is given for
progression.
As long as the drive remains in fixed stop, the position setpoint is adjusted to the actual
position value (position setpoint = actual position value). Fixed stop monitoring and controller
enable are active.
Note
If the drive is in fixed stop, it can can be referenced using the control signal "set reference
point."
If the axis moves away from the position that it had at detection of the fixed stop by more
than the selected monitoring window for the fixed stop (p2635), then the status bit r2683.12
is reset. At the same time, the speed setpoint is set to zero, and fault F07484 "fixed stop
outside of the monitoring window" is triggered with the reaction OFF3 (quick stop). The
monitoring window can be set using parameter p2635 (Fixed stop monitoring window). It
applies to both positive and negative traversing directions and must be selected in such a
way that only a breaking away causes the alarm to be triggered.
Vue de la page 395
1 2 ... 391 392 393 394 395 396 397 398 399 400 401 ... 529 530

Commentaires sur ces manuels

Pas de commentaire