Functions, monitoring, and protective functions
9.3 Drive functions
Drive converter cabinet units
Operating Instructions, 10/2008, A5E00288214A
339
Unit groups
Each parameter that can be switched is assigned to a unit group which can be switched
within certain limits depending on the group.
This assignment and the units groups for each parameter appear in the parameter list in the
SINAMICS List Manual.
The unit groups can be individually switched using 4 parameters (p0100, p0349, p0505 and
p0595).
Parameter
• p0010
Commissioning parameter filter
• p0100
IEC/NEMA mot stds
• p0349
Selection of units system, motor equivalent circuit diagram data
• p0505
Selection of units system
• p0595
Selection of technological unit
• p0596
Reference variable of technological unit
• p2000
Reference frequency/speed
• p2001
Reference voltage
• p2002
Reference current
• p2003
Reference torque
• p2004
Reference power
• p2005
Reference angle
• p2007
Reference acceleration
9.3.14 Derating behavior at increased pulse frequency
Description
To reduce motor noise or to increase output frequency, the pulse frequency can be
increased relative to the factory setting.
The increase in the pulse frequency normally results in a reduction of the maximum output
current (see "Technical data/current derating depending on the pulse frequency").
When commissioning the converter the behavior at overload is adjusted in such a manner
that the pulse frequency is variably reduced so that the required power can be obtained.